Appendix A Runtime Templates Get Generic Value FCM
3BUR002418-600 A 275
ATTRIBUTE NAME Field
This field specifies the mnemonic of the source parameter. An entry must be made
to this field. Valid entry is a parameter mnemonic.
DATAQUAL ATTRIBUTE Field
This field specifies the parameter from which to obtain the data quality of the
parameter named in the ATTRIBUTE NAME field. When this parameter is obtained
it is stored in the data quality of the result parameter (DATAQUAL). Valid entry is a
parameter mnemonic.
ALARM CONDITION Field
This field is used to get the current status of an alarm for the parameter named in the
ATTRIBUTE NAME field. This field specifies the type of alarm to check. It must be
appropriate for the entry in the ATTRIBUTE NAME field. For example, the SETPT
HI entry for this field should only be used when the entry in the ATTRIBUTE
NAME field is a setpoint. You can check only one alarm for a variable. The alarm
status becomes the result of the Get FCM. Valid entries are:
NONE do not obtain an alarm state
DQ BAD measured variable bad data quality alarm
HIHI measured variable high high alarm
HI measured variable high alarm
LO measured variable low alarm
LOLO measured variable low low alarm
IROC HI measured variable input rate of change alarm
OUT DQ B output bad data quality alarm
OUT HI output high alarm
OUT LO output low alarm
OUT IRC output rate of change alarm
SETPT DQ setpoint bad data quality alarm