DO814 Appendix A Runtime Templates
314 3BUR002418-600 A
MONITOR POWER
To monitor process power source enter a YES; if not needed enter a NO.
Default Value is NO.
OSP HOLD 01 through 16
If an OSP TIMEOUT has occurred, will the DO814 hold the last value during OSP?
Enter a YES if it will, or enter a NO if an OSP VALUE will be used.
The Default is NO.
OSP TIMEOUT
Enter the time (msec) after communications is lost, that outputs go to OSP value.
The valid values are:
OFF, 256, 512, and 1024.
The default value is 1024.
OSP VALUE 01 through 16
Enter the channel value (0 or 1) to output after an OSP TIMEOUT. If the OSP
HOLD has been selected as the OSP value then this field entry is ignored.
The valid values are:
0 or 1.
Where 0 = off and 1 = on.
The default is 0.
POSITION
Enter a number from 1 to 12 representing the position of the I/O module relative to
the FCI. The I/O module directly next to the FCI is number 1.
Default value is 1.