AI1 or AI2 as a Pt100, Pt1000, PTC or KTY84 sensor input
Three Pt100/Pt1000 sensors or one KTY84 sensor for motor temperature measurement
can be connected between an analog input and output as shown below. (Alternatively, you
can connect the KTY to an FIO-11 or FAIO-01 analog I/O extension module or FEN-xx
encoder interface module.) At the sensor end of the cable, leave the shields unconnected
or ground them indirectly via a high-frequency capacitor with a few nanofarads, eg. 3.3 nF
/ 630 V. The shield can also be grounded directly at both ends if they are in the same ground
line with no significant voltage drop between the end points.
XAI
XAO
AIn+
AIn-
AOn
AGND
1)
2)
T
TT
13 × Pt100/Pt1000/PTC or 1 × KTY84
1)
Set the input type to voltage with the appropriate switch or jumper on the inverter control
unit. Make the corresponding setting in the inverter unit control program in parameter group
12 Standard AI.
2)
Select the excitation mode in parameter group 13 Standard AO of inverter unit control
program.
WARNING!
As the inputs pictured above are not insulated according to IEC/EN 60664, the
connection of the motor temperature sensor requires double or reinforced insulation
between motor live parts and the sensor. If the assembly does not fulfill the
requirement, the I/O board terminals must be protected against contact and must
not be connected to other equipment or the temperature sensor must be isolated
from the I/O terminals.
DIIL input
The DIIL input is used for the connection of safety circuits. The input is parametrized to stop
the unit when the input signal is lost.
Drive-to-drive link (XD2D)
Note:
On the ACS880-07CLC, the XD2D connector on the supply control unit (A51) is reserved
for cooling fan monitoring. See the ACS880 distributed I/O bus supplement
(3AXD50000126880 [English]).
The drive-to-drive link is a daisy-chained RS-485 transmission line that allows basic
master/follower communication with one master drive and multiple followers.