Factory-installed brake choppers and resistors
Brake choppers (option +D150) and resistors (+D151) are available for the drive as
factory-installed. The factory-installed chopper unit can also be used with a custom resistor
assembly.
The required braking power can be selected according to the application. The ratings of
standard choppers and chopper/resistor combinations are listed under Technical data. For
other braking powers, contact your local ABB representative.
"ACS880-607LC" refers to the brake unit type.
Technical data
Ratings of chopper units (without resistors)
Duty cycle
(10/60 s)
Duty cycle
(1/5 min)
P
cont
I
rms
I
max
R
n
P
brmax
Module type
ACS880-
607LC-…
I
rms
P
br
I
rms
P
br
AkWAkWkWAAohmkW
U
N
= 690 V (Range 525…690 V)
3614042672981191074142.72404NBRW-669C0400-7
7228085345962382148282.728072 × NBRW-669C0800-7
1083121280189435732112422.7212113 × NBRW-669C1200-7
144416161068119247642816562.7216154 × NBRW-669C1600-7
180520201335149059553520702.7220195 × NBRW-669C2000-7
216624241602178871464224842.7224226 × NBRW-669C2400-7
Ratings of standard chopper/resistor combinations
E
R
Duty cycle
(10/60 s)
Duty cycle
(1/5 min)
P
brcont
I
rms
I
max
R
min
P
brmax
Resistor type
Module
type
ACS880-
607LC-…
I
rms
P
br
I
rms
P
br
kJAkWAkWkWAAohmkW
U
N
= 690 V (Range 525…690 V)
1080025728714916754978351.354042 ×
SAFUR200F500
NBRW-
669C
0400-7
2160051457529833310819416701.358072 × (2 ×
SAFUR200F500)
2 ×
NBRW-
669C
0800-7
3240077186244750016229125051.3512113 × (2 ×
SAFUR200F500)
3 ×
NBRW-
669C
1200-7
432001028115059666721638833401.3516154 × (2 ×
SAFUR200F500)
4 ×
NBRW-
669C
1600-7
540001285143774583327048541751.3520195 × (2 ×
SAFUR200F500)
5 ×
NBRW-
669C
2000-7