EasyManua.ls Logo

ABB ACS880-07CLC

ABB ACS880-07CLC
214 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Input cable sizes
This table gives typical cable sizes for:
Marine-type cable with copper conductors such as Nexans MPRXCX
®
FLEXISHIP
®
EMC 0.6/1 (1.2) kV
Industrial-type aluminum and copper cable types. The cable sizing is based on max. 9
cables laid on the cable trays side by side, three ladder type trays one on top of the
other, ambient temperature 30 °C (EN 60204-1 and IEC 60364-5-52). A correction factor
K = 0.70 is used.
Industrial-type cableMarine-type cable
ACS880-07CLC-…
Copper with PVC
insulation
Aluminum with PVC
insulation
Aluminum with
XLPE insulation
Copper
mm
2
mm
2
mm
2
mm
2
U
N
= 690 V, 6-pulse connection
2 × (3 × 150 + 70)2 × (3 × 185 + 57 Cu)2 × (3 × 120 + 41 Cu)3 × (3 × 95)0390A-7
2 × (3 × 150 + 70)2 × (3 × 240 + 72 Cu)2 × (3 × 150 + 41 Cu)3 × (3 × 95)0430A-7
2 × (3 × 150 + 70)2 × (3 × 240 + 72 Cu)2 × (3 × 185 + 57 Cu)3 × (3 × 95)0480A-7
2 × (3 × 185 + 95)3 × (3 × 150 + 41 Cu)2 × (3 × 185 + 57 Cu)3 × (3 × 95)0530A-7
2 × (3 × 240 + 120)3 × (3 × 185 + 57 Cu)2 × (3 × 240 + 72 Cu)4 × (3 × 95)0600A-7
3 × (3 × 150 + 70)3 × (3 × 240 + 72 Cu)3 × (3 × 150 + 41 Cu)4 × (3 × 95)0670A-7
3 × (3 × 185 + 95)3 × (3 × 240 + 72 Cu)3 × (3 × 185 + 57 Cu)5 × (3 × 95)0750A-7
4 × (3 × 150 + 70)4 × (3 × 185 + 57 Cu)3 × (3 × 240 + 72 Cu)5 × (3 × 95)0850A-7
2 × 2 × (3 × 185 + 95)
2 × 3 × (3 × 150 + 41
Cu)
2 × 2 × (3 × 185 + 57
Cu)
2 × 3 × (3 × 95)1030A-7
2 × 2 × (3 × 240 +
120)
2 × 3 × (3 × 185 + 57
Cu)
2 × 2 × (3 × 240 + 72
Cu)
2 × 4 × (3 × 95)1170A-7
2 × 2 × (3 × 240 +
120)
2 × 3 × (3 × 240 + 72
Cu)
2 × 3 × (3 × 150 + 41
Cu)
2 × 4 × (3 × 95)1310A-7
2 × 3 × (3 × 185 + 95)
2 × 3 × (3 × 240 + 72
Cu)
2 × 3 × (3 × 185 + 57
Cu)
2 × 5 × (3 × 95)1470A-7
2 × 3 × (3 × 185 + 95)
2 × 4 × (3 × 185 + 57
Cu)
2 × 3 × (3 × 240 + 72
Cu)
2 × 5 × (3 × 95)1660A-7
3 × 2 × (3 × 240 +
120)
3 × 3 × (3 × 240 + 72
Cu)
3 × 4 × (3 × 120 + 41
Cu)
3 × 4 × (3 × 95)1940A-7
3 × 3 × (3 × 150 + 70)
3 × 3 × (3 × 240 + 72
Cu)
3 × 4 × (3 × 150 + 41
Cu)
3 × 4 × (3 × 120)2180A-7
3 × 3 × (3 × 185 + 95)
3 × 4 × (3 × 185 + 57
Cu)
3 × 4 × (3 × 150 + 41
Cu)
3 × 4 × (3 × 120)2470A-7
4 × 3 × (3 × 150 + 70)
4 × 3 × (3 × 240 + 72
Cu)
4 × 3 × (3 × 185 + 57
Cu)
4 × 3 × (3 × 150)2880A-7
4 × 3 × (3 × 185 + 95)
4 × 3 × (3 × 240 + 72
Cu)
4 × 4 × (3 × 150)3260A-7
U
N
= 690 V, 12-pulse connection
2 × (3 × 185 + 95)
2 × 2 × (3 × 95 + 29
Cu)
2 × (3 × 185 + 57 Cu)2 × 2 × (3 × 95)0530A-7+A004
2 × (3 × 240 + 120)
2 × 2 × (3 × 120 + 41
Cu)
2 × (3 × 240 + 72 Cu)2 × 2 × (3 × 95)0600A-7+A004
2 × 2 × (3 × 95 + 50)
2 × 2 × (3 × 150 + 41
Cu)
2 × 2 × (3 × 95 + 29
Cu)
2 × 2 × (3 × 95)0670A-7+A004
Technical data 161

Table of Contents

Other manuals for ABB ACS880-07CLC

Related product manuals