60 m (200 ft) between external power supply and first inverter unit
30 m (100 ft) between BCU control unit and last inverter module in the chain.
Note:
The voltage at the INx terminals of each inverter control unit (or frame R8i inverter module)
must be at least 17 V DC to be interpreted as “1”.
Grounding of protective shields
Ground the shield in the cabling between the activation switch and the control unit at
the control unit.
Ground the shield in the cabling between two control units at one control unit only.
Do not ground the shield in the cabling between BCU and R8i module, or between R8i
modules.
The Safe torque off function 191