Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Configuration of standard analog outputs.Standard AO13
- / real32Displays the value of AO1 in mA.
This parameter is read-only.
AO1 actual value13.11
1000 = 1 mA / 1000 =
1 mA
Value of AO1.0.000 ... 22.000 mA
Motor speed used /
uint32
Selects a signal to be connected to analog output AO1.
Alternatively, sets the output to excitation mode to
feed a constant current to a temperature sensor.
AO1 source13.12
0NoneZero
11.1 Motor speed used (page 134).Motor speed used
31.6 Output frequency (page 134).Output frequency
41.7 Motor current (page 134).Motor current
61.10 Motor torque (page 134).Motor torque
71.11 DC voltage (page 135).DC voltage
81.14 Output power (page 135).Power inu out
1023.1 Speed ref ramp input (page 270).Speed ref ramp in
1123.2 Speed ref ramp output (page 270).Speed ref ramp out
1224.1 Used speed reference (page 277).Speed ref used
1326.2 Torque reference used (page 297).Torq ref used
See Terms and abbreviations (page 130).Other [value]
20The output is used to feed an excitation current to 1…3
Pt100 sensors. See section Motor thermal
protection (page 111).
Force Pt100
excitation
21The output is used to feed an excitation current to a
KTY84 sensor. See section Motor thermal
protection (page 111).
Force KTY84
excitation
22The output is used to feed an excitation current to 1…3
PTC sensors. See section Motor thermal
protection (page 111).
Force PTC excitation
23The output is used to feed an excitation current to 1…3
Pt1000 sensors. See section Motor thermal
protection (page 111).
Force Pt1000
excitation
3713.91 AO1 data storage (page 197).AO1 data storage
3813.92 AO2 data storage (page 197).AO2 data storage
192 Parameters