Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Language selection; access levels; macro selection;
parameter save and restore; control unit reboot; user
System96
parameter sets; unit selection; data logger triggering;
parameter checksum calculation; user lock.
- / uint16Selects the language of the parameter interface and
other displayed information when viewed on the control
panel.
Language96.1
Note: Not all languages listed below are necessarily
supported.
Note: This parameter does not affect the languages
visible in the Drive Composer PC tool. (Those are
specified under View Settings.)
1033English.English
0 / uint32Pass codes can be entered into this parameter to
activate further access levels (see parameter 96.3
Access levels active) or to configure the user lock.
Pass code96.2
Entering "358" toggles the parameter lock, which
prevents the changing of all other parameters through
the control panel or the Drive Composer PC tool.
Entering the user pass code (by default, "10000000")
enables parameters 96.100 96.102, which can be
used to define a new user pass code and to select the
actions that are to be prevented.
Entering an invalid pass code will close the user lock if
open, i.e. hide parameters 96.100 96.102. After
entering the code, check that the parameters are in
fact hidden. If they are not, enter another (random)
pass code.
Entering several invalid pass codes introduces a delay
before a new attempt can be made. Entering further
invalid codes will progressively lengthen the delay.
Note: You must change the default user pass code to
maintain a high level of cybersecurity. Store the code
in a safe place the protection cannot be disabled even
by ABB if the code is lost.
See also section User lock (page 123).
1 = 1Pass code.0…99999999
- / uint16Shows which access levels have been activated by pass
codes entered into parameter 96.2 Pass code.
Access levels active96.3
Note: This parameter is read-only.
End user.End userb0
Service.Serviceb1
Advanced programmer.Advanced
programmer
b2
.b3…10
OEM access level 1.OEM access level 1b11
OEM access level 2.OEM access level 2b12
516 Parameters