Configuration of maintenance timers/counters.Generic timer &
counter
33
See also section Maintenance timers and
counters (page 118).
- / uint16Displays the maintenance timer/counter status word,
indicating which maintenance timers/counters have
exceeded their limits.
Counter status33.1
This parameter is read-only.
1 = On-time timer 1 has reached its preset limit.On-time 1b0
1 = On-time timer 2 has reached its preset limit.On-time 2b1
1 = Signal edge counter 1 has reached its preset limit.Edge 1b2
1 = Signal edge counter 2 has reached its preset limit.Edge 2b3
1 = Value counter 1 has reached its preset limit.Value 1b4
1 = Value counter 2 has reached its preset limit.Value 2b5
Reservedb6…15
1 = 10000h…FFFFh
- / uint32Displays the actual present value of on-time timer 1.
The timer runs whenever the signal selected by
parameter 33.13 On-time 1 source is on.
On-time 1 actual33.10
When the timer exceeds the limit set by 33.11 On-time
1 warn limit, bit 0 of 33.1 Counter status is set to 1. The
warning specified by 33.14 On-time 1 warn message is
also given if enabled by 33.12 On-time 1 function.
The timer can be reset from the Drive Composer PC
tool, or from the control panel by keeping Reset
depressed for over 3 seconds.
- / -Actual present value of on-time timer 1.0...4294967295 s
- / uint32Sets the warning limit for on-time timer 1.On-time 1 warn limit33.11
- / -Warning limit for on-time timer 1.0...4294967295 s
- / uint16Configures on-time timer 1.On-time 1 function33.12
0 = Loop: When the limit is reached, the counter is reset.
The counter status (bit 0 of 33.1) switches to 1 for one
Counter modeb0
second. The warning (if enabled) stays active for at
least 10 seconds.
1 = Saturate: When the limit is reached, the counter
status (bit 0 of 33.1) switches to 1, and remains so until
33.10 is reset. The warning (if enabled) also stays active
until 33.10 is reset.
0 = Disable: No warning is given when the limit is
reached
Warning enableb1
1 = Enable: A warning (see 33.14) is given when the limit
is reached
Reservedb2…15
1 = 10000h…FFFFh
False / uint32Selects the signal to be monitored by on-time timer 1.On-time 1 source33.13
0Constant 0 (timer disabled).False
332 Parameters