Voltage control and trip limits
The control and trip limits of the intermediate DC voltage regulator are relative to
the supply voltage as well as drive/inverter type. The DC voltage is approximately
1.35 times the line-to-line supply voltage, and is displayed by parameter 1.11.
All levels are relative to the supply voltage range selected in parameter 95.1. The
following table shows the values of selected DC voltage levels in volts and in percent
of
U
DCmax
(the DC voltage at the upper bound of the supply voltage range).
Supply voltage range [V AC] (see 95.1)
660...690525...600500440...480380...415208...240Level [V DC (% of
U
DCmax
)]
12181113880878800
489/440
1)
Overvoltage fault limit
1167
(125)
1013
(125)
810
(120)
810
(125)
700
(125)
405
(125)
Overvoltage control limit
1159
(124)
1008
(124)
806
(119)
806
(124)
697
(124)
403
(124)
Internal brake chopper at 100%
pulse width
1077
(116)
936
(116)
780
(116)
749
(116)
648
(116)
375
(116)
Internal brake chopper at 0% pulse
width
1071
(115)
932
(115)
776
(115)
745
(115)
644
(115)
373
(115)
Overvoltage warning limit
932
(100)
810
(100)
675
(100)
648
(100)
560
(100)
324
(100)
U
DCmax
= DC voltage at upper
bound of supply voltage range
891709675594513281DC voltage at lower bound of supply
voltage range
757 (85)602 (85)574 (85)505
(85)
436 (85)239 (85)Undervoltage control and warning
limit
713 (80)567 (80)540
(80)
475 (80)410 (80)225 (80)Charging activation/standby limit
535 (60)425 (60)405
(60)
356 (60)308
(60)
168 (60)Undervoltage fault limit
1)
489 V with frames R1…R3, 440 V with frames R4…R8.
Settings and diagnostics
Parameters: 1.11 DC voltage (page 135), 30.30 Overvoltage control (page 312), 30.31
Undervoltage control (page 313), 95.1 Supply voltage (page 507), and 95.2 Adaptive
voltage limits (page 507).
Program features 105