STATE/DescriptionValueNameBit
Accelerate to jogging 2 reference.1JOGGING_29
See notes at bit 8.
Jogging 2 disabled.0
Fieldbus control enabled.1REMOTE_ CMD10
Control word and reference will not get through
to the drive, except for CW bits OFF1, OFF2 and
OFF3.
0
Select External Control Location EXT2. Effective
if the control location is parameterized to be se-
lected from the fieldbus.
1EXT_CTRL_ LOC11
Select External Control Location EXT1. Effective
if the control location is parameterized to be se-
lected from the fieldbus.
0
Reserved12...15
Status Word
The table below shows the fieldbus Status Word for the ABB Drives control profile.
The embedded fieldbus interface converts the drive Status Word into this form
for the fieldbus. The upper case boldface text refers to the states shown in State
transition diagram (page 616).
STATE/DescriptionValueNameBit
READY TO SWITCH ON.1RDY_ON0
NOT READY TO SWITCH ON.0
READY TO OPERATE.1RDY_RUN1
OFF1 ACTIVE.0
OPERATION ENABLED.1RDY_REF2
OPERATION INHIBITED.0
FAULT.1TRIPPED3
No fault.0
OFF2 inactive.1OFF_2_STA4
OFF2 ACTIVE.0
OFF3 inactive.1OFF_3_STA5
OFF3 ACTIVE.0
SWITCH-ON INHIBITED.1SWC_ON_ INHIB6
-0
Warning/Alarm.1ALARM7
No warning/alarm.0