Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Configuration of standard analog inputs.Standard AI12
No action / uint16Triggers the analog input tuning function.
Connect the signal to the input and select the
appropriate tuning function.
AI tune12.1
0AI tune is not activated.No action
1Current analog input AI1 signal value is set as minimum
value of AI1 into parameter 12.17 AI1 min. The value
reverts back to No action automatically.
AI1 min tune
2Current analog input AI1 signal value is set as maximum
value of AI1 into parameter 12.18 AI1 max. The value
reverts back to No action automatically.
AI1 max tune
3Current analog input AI2 signal value is set as minimum
value of AI2 into parameter 12.27 AI2 min. The value
reverts back to No action automatically.
AI2 min tune
4Current analog input AI2 signal value is set as maximum
value of AI2 into parameter 12.28 AI2 max. The value
reverts back to No action automatically.
AI2 max tune
No action / uint16Selects how the drive reacts when an analog input
signal moves out of the minimum and/or maximum
limits specified for the input.
AI supervision
function
12.3
The supervision applies a margin of 0.5 V or 1.0 mA to
the limits. For example, if the maximum limit for the
input is 7.000 V, the maximum limit supervision
activates at 7.500 V.
The inputs and the limits to be observed are selected
by parameter 12.4 AI supervision selection.
Note: Analog input signal supervision is only active
when
the analog input is set as the source (using the
AI1 scaled or AI2 scaled selection) in parameter
22.11, 22.12, 22.15, 22.17, 23.42, 26.11, 26.12, 26.16,
26.25, 30.21, 30.22, or 44.9, and is being used as
the active source, or
supervision is forced using parameter 12.5 AI
supervision force.
0No action taken.No action
1Drive trips on 80A0 AI Supervision.Fault
2Drive generates an A8A0 AI Supervised Warning
warning.
Warning