Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Configuration of encoder interface modules.Encoder module
settings
91
- / uint16Displays the status of the digital inputs of FEN-xx
encoder interface modules.
FEN DI status91.1
Note: This parameter is read-only.
DI1 of interface module 1 (see parameters 91.11 and
91.12)
DI1 /module 1b0
DI2 of interface module 1 (see parameters 91.11 and
91.12)
DI2 /module 1b1
Reservedb2…3
DI1 of interface module 2 (see parameters 91.13 and
91.14)
DI1 /module 2b4
DI2 of interface module 2 (see parameters 91.13 and
91.14)
DI2 /module 2b5
Reservedb6…15
1 = 10000h…FFFFh
- / uint16Displays the type of the interface module found in the
location specified by parameter 91.12 Module 1 location.
Module 1 status91.2
Note: This parameter is read-only.
0No module detected in the specified slot.No option
1A module has been detected but cannot be
communicated with.
2The module type is unknown.
16An FEN-01 module has been detected and is active.FEN-01
17An FEN-11 module has been detected and is active.FEN-11
18An FEN-21 module has been detected and is active.FEN-21
21An FEN-31 module has been detected and is active.FEN-31
25An FSE-31 module has been detected and is active.FSE-31
- / uint16Displays the type of the interface module found in the
location specified by parameter 91.14 Module 2 location.
Module 2 status91.3
For the indications, see parameter 91.2 Module 1 status.
Note: This parameter is read-only.
- / real32Displays the temperature measured through the sensor
input of interface module 1. The unit (°C or °F) is
selected by parameter 96.16 Unit selection.
Module 1
temperature
91.4
Note: With a PTC sensor, the unit is ohms.
Note: This parameter is read-only.
- / -Temperature measured through interface module 1.0.0 ... 1000.0 °