EasyManua.ls Logo

ABB ACS880 N5700 Series - Motor Thermal Protection

ABB ACS880 N5700 Series
662 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Motor thermal protection settings such as temperature
measurement configuration, load curve definition and
motor fan control configuration.
Motor thermal
protection
35
See also section Motor thermal protection (page 111).
- / real32Displays the motor temperature as estimated by the
internal motor thermal protection model (see
Motor estimated
temperature
35.1
parameters 35.5035.55). The unit (°C or °F) is selected
by parameter 96.16 Unit selection.
This parameter is read-only.
1 = 1 ° / 1 = 1 °Estimated motor temperature.-60.0 ... 1000.0 °
- / real32Displays the temperature received through the source
defined by parameter 35.11 Temperature 1 source. The
unit is selected by parameter 96.16 Unit selection.
Measured
temperature 1
35.2
Note: With °F, the range is -76…1832. With a PTC sensor,
the range is 0…5000 ohms.
This parameter is read-only.
1 = 1 ° / 1 = 1 °Measured temperature 1.-60...1000 °
- / real32Displays the temperature received through the source
defined by parameter 35.21 Temperature 2 source. The
unit is selected by parameter 96.16 Unit selection.
Measured
temperature 2
35.3
Note: With °F, the range is -76…1832. With a PTC sensor,
the range is 0…5000 ohms.
This parameter is read-only.
1 = 1 ° / 1 = 1 °Measured temperature 2.-60...1000 °
- / uint16Displays the status of optional FPTC-xx thermistor
protection modules. The word can be used as the
source of eg. external events.
FPTC status word35.4
Note: The “module found” bits are updated regardless
of whether the corresponding module is activated.
However, the “fault active” and “warning active” bits
are not updated if the module is not activated. Modules
are activated by parameter 35.30 FPTC configuration
word.
This parameter is read-only.
1 = Yes: An FPTC-xx module has been detected in slot
1.
Module found in slot
1
b0
1 = Yes: The module in slot 1 has an active fault (4991
Safe motor temperature 1).
Fault active in slot 1b1
1 = Yes: The module in slot 1 has an active warning (A497
Motor temperature 1).
Warning active in
slot 1
b2
1 = Yes: An FPTC-xx module has been detected in slot
2.
Module found in slot
2
b3
1 = Yes: The module in slot 2 has an active fault (4992
Safe motor temperature 2).
Fault active in slot 2b4
1 = Yes: The module in slot 2 has an active warning
(A498 Motor temperature 2).
Warning active in
slot 2
b5
340 Parameters

Table of Contents

Related product manuals