Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Start and stop modes; emergency stop mode and signal
source selection; DC magnetization settings;
autophasing mode selection.
Start/stop mode21
Automatic / uint16Selects the motor start function for the DTC motor
control mode, ie. when 99.4 Motor control mode is set
to DTC.
Start mode21.1
Note:
The start function for the scalar motor control
mode is selected by parameter 21.19 Scalar start
mode.
Starting into a rotating motor is not possible when
DC magnetizing is selected (Fast or Constant
time).
With permanent magnet motors and synchronous
reluctance motors, Automatic start mode must
be used.
This parameter cannot be changed while the drive
is running.
See also section DC magnetization (page 93).
0The drive pre-magnetizes the motor before start. The
premagnetizing time is determined automatically,
Fast
being typically 200 ms to 2 s depending on motor size.
This mode should be selected if a high break-away
torque is required.
1The drive pre-magnetizes the motor before start. The
premagnetizing time is defined by parameter 21.2
Constant time
Magnetization time. This mode should be selected if
constant pre-magnetizing time is required (e.g. if the
motor start must be synchronized with the release of
a mechanical brake). This setting also guarantees the
highest possible break-away torque when the
pre-magnetizing time is set long enough.
WARNING!
The drive will start after the set magnetizing
time has passed even if motor magnetization
is not completed. In applications where a full
break-away torque is essential, ensure that the
constant magnetizing time is long enough to
allow generation of full magnetization and
torque.