Contents of the fieldbus Status word (ABB Drives profile)
The upper case boldface text refers to the states shown in the state diagram (page
575).
STATE/DescriptionValueNameBit
READY TO SWITCH ON.1Ready to switch
ON
0
NOT READY TO SWITCH ON.0
READY TO OPERATE.1Ready run1
OFF1 ACTIVE.0
OPERATION ENABLED.1Ready ref2
OPERATION INHIBITED. See parameters 6.18 Start in-
hibit status word and 6.25 Drive inhibit status word 2
for the inhibiting condition.
0
FAULT.1Tripped3
No fault.0
OFF2 inactive.1Off 2 inactive4
OFF2 ACTIVE.0
OFF3 inactive.1Off 3 inactive5
OFF3 ACTIVE.0
SWITCH-ON INHIBITED.1Switch-on
inhibited
6
–0
Warning active.1Warning7
No warning active.0
OPERATING. Actual value equals reference = is within
tolerance limits (see parameters 46.21…46.23).
1At setpoint8
Actual value differs from reference = is outside toler-
ance limits.
0
Drive control location: REMOTE (EXT1 or EXT2).1Remote9
Drive control location: LOCAL.0
See parameter 6.29 MSW bit 10 sel.-Above limit10
See parameter 6.30 MSW bit 11 sel.-User bit 011
See parameter 6.31 MSW bit 12 sel.-User bit 112
See parameter 6.32 MSW bit 13 sel.-User bit 213
See parameter 6.33 MSW bit 14 sel.-User bit 314
Reserved.15
Fieldbus control through a fieldbus adapter 635