Standard connections for speed control
In speed control mode with default settings, the reference signal is connected to
analog input AI1. The start/stop commands are given through digital input DI1;
running direction is determined by DI2. This macro uses control location EXT1.
Faults are reset through digital input DI3.
DI4 switches between acceleration/deceleration time sets 1 and 2. The acceleration
and deceleration times, as well as ramp shapes, are defined by parameters
23.12…23.19.
DI5 activates constant speed 1.
Default control connections in speed control
DescriptionTermConnection
XPOW External power input
24 V DC, 2 A
+24VI
1
2
+24VI
GND
GND
XAI Reference voltage and analog inputs
10 V DC,
R
L
1…10 kohm+VREF
+VREF
-VREF
AGND
AI1+
AI1-
AI2+
AI2-
1
2
3
4
5
6
7
-10 V DC,
R
L
1…10 kohm-VREF
GroundAGND
Speed reference
0(2)…10 V,
R
in
> 200 kohm
AI1+
AI1-
By default not in use.
0(4)…20 mA,
R
in
= 100 ohm
AI2+
AI2-
XAO Analog outputs
Motor speed rpmAO1
AO1
AGND
AO2
AGND
1
2
3
4
0…20 mA,
R
L
< 500 ohm
AGND
Motor current
0…20 mA,
R
L
< 500 ohm
AO2
AGND
XD2D Drive-to-drive link
Master/follower, drive-to-drive or embed-
ded fieldbus interface connection
B
1
2
3
B
A
BGND
A
BGND
30 Default control connections