Motor values supplied by the user that are used in the
motor model.
User motor
parameters
98
These parameters are useful for non-standard motors,
or to just get more accurate motor control of the motor
on site. A better motor model always improves the
shaft performance.
Not selected / uint16Activates the motor model parameters 98.2 98.14
and the rotor angle offset parameter 98.15.
User motor model
mode
98.1
Note: Parameter value is automatically set to zero when
ID run is selected by parameter 99.13 ID run requested.
The values of parameters 98.2 98.15 are then updated
according to the motor characteristics identified during
the ID run.
Note: Measurements made directly from the motor
terminals during the ID run are likely to produce slightly
different values than those on a datasheet from a
motor manufacturer.
Note: This parameter cannot be changed while the
drive is running.
0The values detected during the ID run are being used.Not selected
1The values of parameters 98.2 98.14 are used in the
motor model.
Motor parameters
2The value of parameter 98.15 is used as the rotor angle
offset. Parameters 98.2 98.14 are inactive.
Position offset
3The values of parameters 98.2 98.14 are used in the
motor model, and the value of parameter 98.15 is used
as the rotor angle offset.
Motor parameters &
position offset
0.00000 pu / real32Defines the stator resistance
R
S
of the motor model.
With a star-connected motor,
R
S
is the resistance of
one winding. With a delta-connected motor,
R
S
is
one-third of the resistance of one winding.
Rs user98.2
Resistance value is given at 20 °C (68 °F).
- / -Stator resistance in per unit.0.00000 ... 0.50000
pu
0.00000 pu / real32Defines the rotor resistance
R
R
of the motor model.
Resistance value is given at 20 °C (68 °F).
Rr user98.3
Note: This parameter is valid only for asynchronous
motors.
- / -Rotor resistance in per unit.0.00000 ... 0.50000
pu
0.00000 pu / real32Defines the main inductance
L
M
of the motor model.
Note: This parameter is valid only for asynchronous
motors.
Lm user98.4
- / -Main inductance in per unit.0.00000 ... 10.00000
pu
Parameters 533