Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Motor values supplied by the user that are used in the
motor model.
User motor
parameters
98
These parameters are useful for non-standard motors,
or to just get more accurate motor control of the motor
on site. A better motor model always improves the
shaft performance.
Not selected / uint16Activates the motor model parameters 98.2 … 98.14
and the rotor angle offset parameter 98.15.
User motor model
mode
98.1
Note: Parameter value is automatically set to zero when
ID run is selected by parameter 99.13 ID run requested.
The values of parameters 98.2 … 98.15 are then updated
according to the motor characteristics identified during
the ID run.
Note: Measurements made directly from the motor
terminals during the ID run are likely to produce slightly
different values than those on a datasheet from a
motor manufacturer.
Note: This parameter cannot be changed while the
drive is running.
0The values detected during the ID run are being used.Not selected
1The values of parameters 98.2 … 98.14 are used in the
motor model.
Motor parameters
2The value of parameter 98.15 is used as the rotor angle
offset. Parameters 98.2 … 98.14 are inactive.
Position offset
3The values of parameters 98.2 … 98.14 are used in the
motor model, and the value of parameter 98.15 is used
as the rotor angle offset.
Motor parameters &
position offset
0.00000 pu / real32Defines the stator resistance
R
S
of the motor model.
With a star-connected motor,
R
S
is the resistance of
one winding. With a delta-connected motor,
R
S
is
one-third of the resistance of one winding.
Rs user98.2
Resistance value is given at 20 °C (68 °F).
- / -Stator resistance in per unit.0.00000 ... 0.50000
pu
0.00000 pu / real32Defines the rotor resistance
R
R
of the motor model.
Resistance value is given at 20 °C (68 °F).
Rr user98.3
Note: This parameter is valid only for asynchronous
motors.
- / -Rotor resistance in per unit.0.00000 ... 0.50000
pu
0.00000 pu / real32Defines the main inductance
L
M
of the motor model.
Note: This parameter is valid only for asynchronous
motors.
Lm user98.4
- / -Main inductance in per unit.0.00000 ... 10.00000
pu
Parameters 533