Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Various run-time-type counters and measurements
related to drive maintenance.
Diagnostics5
All parameters in this group are read-only unless
otherwise noted.
0 d / uint16On-time counter. The counter runs when the drive is
powered.
On-time counter5.1
1 = 1 d / 1 = 1 dOn-time counter.0...65535 d
0 d / uint16Motor run-time counter. The counter runs when the
inverter modulates.
Run-time counter5.2
1 = 1 d / 1 = 1 dMotor run-time counter.0...65535 d
0 d / uint16Running time of the drive cooling fan. Can be reset from
the control panel by keeping Reset depressed for over
3 seconds.
Main fan on-time
counter
5.4
1 = 1 d / 1 = 1 dCooling fan run-time counter.0...65535 d
- / uint32500-microsecond ticks elapsed since the last boot of
the control unit.
Time from power-up5.9
1 = 1 / 1 = 1500-microsecond ticks since last boot.0...4294967295
- / real32Estimated drive temperature in percent of fault limit.
The actual trip temperature varies according to the
type of the drive.
Inverter temperature5.11
0.0 % = 0 °C (32 °F)
94 % approx. = Warning limit
100.0 % = Fault limit
1 = 1 % / 10 = 1 %Drive temperature in percent.-40.0 ... 160.0 %
- / uint16Diagnostic word 3.Diagnostic word 35.22
Reservedb0…10
1 = Drive fan is rotating above idle speedFan commandb11
1 = Drive fan service counter has reached its limitFan service counterb12
Reservedb13…15
1 = 10000h…FFFFh
0 % / real32Displays the age of the main cooling fan as a
percentage of its estimated lifetime. The estimate is
Main fan service
counter
5.41
based on the duty, operating conditions and other
operating parameters of the fan. When the counter
reaches 100%, a warning (A8C0 Fan service counter) is
generated.
Can be reset from the control panel by keeping Reset
depressed for over 3 seconds.
1 = 1 % / 1 = 1 %Main cooling fan age.0...150 %
150 Parameters