EasyManua.ls Logo

ABB ACS880 N5700 Series - Warning Indications; Settings and Diagnostics; Oscillation Damping

ABB ACS880 N5700 Series
662 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
-
+
+
+
+
Derivative
acceleration
compensation
Proportional,
integral
Derivative
Torque
reference
Actual speed
Speed
reference
Error value
Warning indications
A warning message, AF90 will be generated if the autotune routine does not
complete successfully.
For further information, see chapter Fault tracing (page 547).
Settings and diagnostics
Parameters: 25.33 Speed controller autotune25.40 Autotune repeat
times (page 295).
Events: AF90 Speed controller autotuning (page 588).
Oscillation damping
The oscillation damping function can be used to cancel out oscillations caused by
mechanics or an oscillating DC voltage. The input a signal reflecting the oscillation
is selected by parameter 26.53. The oscillation damping function outputs a sine
wave (26.58) which can be summed with the torque reference with a suitable gain
(26.57) and phase shift (26.56).
The oscillation damping algorithm can be activated without connecting the output
to the reference chain, which makes it possible to compare the input and output
of the function and make further adjustments before applying the result.
82 Program features

Table of Contents

Related product manuals