Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
0.00 uF / real32Defines the capacitance of a custom sine filter, i.e. when
parameter 95.15 Special HW settings bit 3 is activated.
If the capacitors are star/wye-connected, enter the
capacitance of one leg into the parameter.
M
3~
C
99.19 = C
C C
Drive
Sine filter
If the capacitors are delta-connected, multiply the
capacitance of one leg by 3 and enter the result into
the parameter.
M
3~
CC
C
99.19 = 3 × C
Drive
Sine filter
Note: For an ABB sine filter (95.15 Special HW settings
bit 1), this parameter is set automatically and should
not be adjusted.
Sine filter
capacitance
99.19
100 = 1 uF / 100 = 1
uF
Capacitance of custom sine filter.0.00 ... 100000.00 uF
Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
FSO-xx settings.
This group contains parameters related to the optional
FSO-xx safety functions module. For details, refer to
the documentation of the FSO-xx module.
Safety200
Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Distributed I/O bus settings.
This group is only visible with a BCU control unit.
This group contain parameters related to the
distributed I/O bus, which is used with some drives for
monitoring the cooling fans of the cabinet system. For
details, refer to
CIO-01 I/O module for distributed I/O
bus control user’s manual
(3AXD50000126880
[English]).
I/O bus
configuration
206
544 Parameters