Data conversion if parameter 58.25 Control profile is set to ABB Drives. See section
About the control profiles (page 612).
2
If parameter 58.25 Control profile is set to Transparent,3
The sources of the status word and actual values are selected by parameters
58.3058.32 (otherwise, actual values 1 and 2 are automatically selected ac-
cording to reference type), and
The control word is displayed by 6.5 EFB transparent control word.
Control word and Status word
The Control Word (CW) is a 16-bit or 32-bit packed boolean word. It is the principal
means of controlling the drive from a fieldbus system. The CW is sent by the
fieldbus controller to the drive. By drive parameters, the user selects the EFB CW
as the source of drive control commands (such as start/stop, emergency stop,
selection between external control locations 1/2, or fault reset). The drive switches
between its states according to the bit-coded instructions of the CW.
The fieldbus CW is either written to the drive as it is (see parameter 6.5 EFB
transparent control word), or the data is converted. See section About the control
profiles (page 612).
The fieldbus Status Word (SW) is a 16-bit or 32-bit packed boolean word. It contains
status information from the drive to the fieldbus controller. The drive SW is either
written to the fieldbus SW as it is or the data is converted. See section About the
control profiles (page 612).
References
EFB references 1 and 2 are 16-bit or 32-bit signed integers. The contents of each
reference word can be used as the source of virtually any signal, such as the speed,
frequency, torque or process reference. In embedded fieldbus communication,
references 1 and 2 are displayed by 3.9 EFB reference 1 and 3.10 EFB reference 2
respectively. Whether the references are scaled or not depends on the settings of
58.26 EFB ref1 type and 58.27 EFB ref2 type. See section About the control
profiles (page 612).
Actual values
Fieldbus actual signals (ACT1 and ACT2) are 16-bit or 32-bit signed integers. They
convey selected drive parameter values from the drive to the master. Whether the
actual values are scaled or not depends on the settings of 58.28 EFB act1 type and
58.29 EFB act2 type. See section About the control profiles (page 612).
Data input/outputs
Data input/outputs are 16-bit or 32-bit words containing selected drive parameter
values. Parameters 58.101 Data I/O 1 58.124 Data I/O 24 define the addresses
from which the master either reads data (input) or to which it writes data (output).