Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Speed supervision settings; actual signal filtering;
general scaling settings.
Monitoring/scaling
settings
46
Note: The 16-bit scalings apply when parameter values
are read or written directly. With protocol- and
profile-specific read/write commands (eg.
communication objects), the scaling depends on the
protocol or profile. See the documentation of the
adapter module.
1500.00; 1800.00 rpm
(95.20 b0) rpm /
real32
Defines the maximum speed value used to define the
acceleration ramp rate and the initial speed value used
to define the deceleration ramp rate (see parameter
group 23 Speed reference ramp). The speed
Speed scaling46.1
acceleration and deceleration ramp times are therefore
related to this value (not to parameter 30.12 Maximum
speed).
Also defines the 16-bit scaling of speed-related
parameters.
The value of this parameter corresponds to 20000 in
fieldbus, master/follower etc. communication.
1 = 1 rpm / 100 = 1
rpm
Acceleration/deceleration terminal/initial speed.0.10 ... 30000.00
rpm
- / real32ReservedFrequency scaling46.2
100.0 % / real32Defines the 16-bit scaling of torque parameters. The
value of this parameter (in percent of nominal motor
Torque scaling46.3
torque) corresponds to 10000 in fieldbus,
master/follower etc. communication.
See also parameter 46.42 Torque decimals.
10 = 1 % / 10 = 1 %Torque corresponding to 10000 on fieldbus.0.1 ... 1000.0 %
1000.00 kW or hp /
real32
Defines the output power value that corresponds to
10000 in fieldbus, master/follower etc. communication.
The unit is selected by parameter 96.16 Unit selection.
Power scaling46.4
1 = 1 kW or hp / 100 =
1 kW or hp
Power corresponding to 10000 on fieldbus.0.10 ... 30000.00 kW
or hp
10000 A / real32Defines the 16-bit scaling of current parameters. The
value of this parameter corresponds to 10000 in
fieldbus, master/follower etc. communication.
Current scaling46.5
1 = 1 A / 1 = 1 ACurrent corresponding to 10000 on fieldbus.0...30000 A
0.00 rpm / real32Defines a speed corresponding to a zero reference
received from fieldbus (either the embedded fieldbus
Speed ref zero
scaling
46.6
interface, or interface FBA A or FBA B). For example,
with a setting of 500, the fieldbus reference range of
0…20000 would correspond to a speed of 500…[46.1]
rpm.
Note: This parameter is effective only with the ABB
Drives communication profile.
1 = 1 rpm / 100 = 1
rpm
Speed corresponding to minimum fieldbus reference.0.00 ... 30000.00
rpm
368 Parameters