EasyManua.ls Logo

ABB ACS880 N5700 Series - Basics of the embedded fieldbus interface

ABB ACS880 N5700 Series
662 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Function/InformationSetting for fieldbus
control
Parameter
Saves parameter value changes (includ-
ing those made through fieldbus control)
to permanent memory.
Save (reverts to Done)96.7 Parameter save
manually
Basics of the embedded fieldbus interface
The cyclic communication between a fieldbus system and the drive consists of
16-bit data words or 32-bit data words (with the transparent control profiles).
The diagram below illustrates the operation of the embedded fieldbus interface.
The signals transferred in the cyclic communication are explained further below
the diagram.
EFB profile
Fieldbus network
Cyclic communication
CW
REF1
REF2
2)
SEL
0
2
EFB CW
3)
03.09 EFB reference 1
03.10 EFB reference 2
EFB SW
3)
Actual 1
3)
Actual 2
3)
1)
EXT1/2
Start commands
0
2
58.25
SW
ACT1
ACT2
Data I/O
selection
Acyclic communication
Parameter
table
Groups
22/26/28/40 etc.
Reference
selection
Groups
22/26/28/40 etc.
Reference
selection
20.01
20.06
Par. 01.01...255.255
2)
I/O 1
I/O 2
I/O 3
...
I/O 24
58.101
58.124
See also other parameters which can be controlled through fieldbus.1
610 Fieldbus control through the embedded fieldbus interface (EFB)

Table of Contents

Related product manuals