Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Peak value and amplitude logger settings.Load analyzer36
See also section Load analyzer (page 119).
Power inu out /
uint32
Selects the signal to be monitored by the peak value
logger.
The signal is filtered using the filtering time specified
by parameter 36.2 PVL filter time.
PVL signal source36.1
The peak value is stored, along with other pre-selected
signals at the time, into parameters 36.1236.15.
The peak value logger can be reset using parameter
36.9 Reset loggers. The logger is also reset whenever
the signal source is changed. The date and time of the
last reset are stored into parameters 36.16 and 36.17
respectively.
0NoneZero
11.1 Motor speed used (page 134).Motor speed used
31.6 Output frequency (page 134).Output frequency
41.7 Motor current (page 134).Motor current
61.10 Motor torque (page 134).Motor torque
71.11 DC voltage (page 135).DC voltage
81.14 Output power (page 135).Power inu out
1023.1 Speed ref ramp input (page 270).Speed ref ramp in
1123.2 Speed ref ramp output (page 270).Speed ref ramp out
1224.1 Used speed reference (page 277).Speed ref used
1326.2 Torque reference used (page 297).Torq ref used
See Terms and abbreviations (page 130).Other [value]
2.00 s / real32Defines a filtering time for the peak value logger. See
parameter 36.1 PVL signal source.
PVL filter time36.2
100 = 1 s / 100 = 1 sPeak value logger filtering time.0.00 ... 120.00 s
Ambient temperature
/ uint32
Selects the signal to be monitored by amplitude logger
2. The signal is sampled at 200 ms intervals, and can
be scaled using parameter 36.7 AL2 signal scaling.
AL2 signal source36.6
The results are displayed by parameters 36.4036.49.
Each parameter represents an amplitude range, and
shows what portion of the samples fall within that
range.
Amplitude logger 2 can be reset using parameter 36.9
Reset loggers. The logger is also reset whenever the
signal source or scaling is changed. The date and time
of the last reset are stored into parameters 36.50 and
36.51 respectively.
0NoneZero
11.1 Motor speed used (page 134).Motor speed used
31.6 Output frequency (page 134).Output frequency
41.7 Motor current (page 134).Motor current
61.10 Motor torque (page 134).Motor torque
Parameters 355