Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
-1500.00; -1800.00
(95.20 b0) rpm /
real32
Defines the minimum allowed speed.
WARNING!
This value must not be higher than 30.12
Maximum speed.
WARNING!
In a master/follower configuration, do not set
maximum and minimum speed limits with the
same sign on a follower drive. See section
Master/follower functionality (page 66).
Minimum speed30.11
- / -Minimum allowed speed. For scaling, see parameter
46.1.
-30000.00 ...
30000.00 rpm
1500.00; 1800.00
(95.20 b0) rpm /
real32
Defines the maximum allowed speed.
WARNING!
This value must not be lower than 30.11
Minimum speed.
WARNING!
In a master/follower configuration, do not set
maximum and minimum speed limits with the
same sign on a follower drive. See section
Master/follower functionality (page 66).
Maximum speed30.12
- / -Maximum speed. For scaling, see parameter 46.1.-30000.00 ...
30000.00 rpm
Disable / uint16A temporary motor current limit specifically for starting
can be defined by this parameter and 30.16 Maximum
start current.
When this parameter is set to Enable, the drive observes
the start current limit defined by 30.16 Maximum start
current. The limit is in force for 2 seconds after initial
magnetization (of an asynchronous induction motor)
or autophasing (of a permanent magnet motor), but
not more often than once in every 7 seconds. Otherwise,
the limit defined by 30.17 Maximum current is in force.
Note: The availability of a start current higher than the
general limit depends on drive hardware. See the rating
data in the hardware manual of the drive.
Maximum start
current enable
30.15
0Start current limit disabled.Disable
1Start current limit enabled.Enable
0.00 A / real32Defines a maximum start current when enabled by
parameter 30.15 Maximum start current enable.
Maximum start
current
30.16
1 = 1 A / 100 = 1 AMaximum start current.0.00 ... 30000.00 A
0.00 A / real32Defines the maximum allowed motor current.Maximum current30.17
308 Parameters