Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
1 = 1 ms / 1 = 1 msMinimum response delay.0...65535 ms
0 / uint32Displays the raw (unmodified) control word sent by the
Modbus controller to the drive. For debugging
purposes.
This parameter is read-only.
EFB control word58.18
1 = 1Control word sent by Modbus controller to the drive.00000000…FFFFFFFFh
0 / uint32Displays the raw (unmodified) status word sent by the
drive to the Modbus controller. For debugging
purposes.
This parameter is read-only.
EFB status word58.19
1 = 1Status word sent by the drive to the Modbus controller.00000000…FFFFFFFFh
ABB Drives / uint16Defines the control profile used by the protocol.Control profile58.25
0ABB Drives profile (with a 16-bit control word) with
registers in the classic format for backward
compatibility.
ABB Drives
2Transparent profile (16-bit or 32-bit control word) with
registers in the classic format.
Transparent
Auto / uint16Selects the type and scaling of reference 1 received
through the embedded fieldbus interface.
The scaled reference is displayed by 3.9 EFB reference
1.
EFB ref1 type58.26
0Type and scaling are chosen automatically according
to which reference chain (see settings Torque, Speed,
Frequency) the incoming reference is connected to. If
the reference is not connected to any chain, no scaling
is applied (as with setting Transparent).
Auto
1No scaling is applied.Transparent
2Generic reference with a scaling of 100 = 1 (ie. integer
and two decimals).
General
3The scaling is defined by parameter 46.3 Torque scaling.Torque
4The scaling is defined by parameter 46.1 Speed scaling.Speed
5The scaling is defined by parameter 46.2 Frequency
scaling.
Frequency
Torque / uint16Selects the type and scaling of reference 2 received
through the embedded fieldbus interface.
The scaled reference is displayed by 3.10 EFB reference
2.
For the selections, see parameter 58.26 EFB ref1 type.
EFB ref2 type58.27
Auto / uint16Selects the type/source and scaling of actual value 1
transmitted to the fieldbus network through the
embedded fieldbus interface.
EFB act1 type58.28
0Type/source and scaling follow the type of reference
1 selected by parameter 58.26 EFB ref1 type. See the
individual settings below for the sources and scalings.
Auto
1The value selected by parameter 58.31 EFB act1
transparent source is sent as actual value 1. No scaling
is applied (the 16- bit scaling is 1 = 1 unit).
Transparent