20 ° / real32Defines the ambient temperature of the motor for the
motor thermal protection model. The unit (°C or °F) is
selected by parameter 96.16 Unit selection.
The motor thermal protection model estimates the
motor temperature on the basis of parameters
35.50…35.55. The motor temperature increases if it
operates in the region above the load curve, and
decreases if it operates in the region below the load
curve.
WARNING!
The model cannot protect the motor if the
motor does not cool properly because of dust,
dirt, etc.
Motor ambient
temperature
35.50
1 = 1 ° / 1 = 1 °Ambient temperature.-60...100 °
100 % / uint16Definesthe motor load curve together with parameters
35.52 Zero speed load and 35.53 Break point. The load
curve is used by the motor thermal protection model
to estimate the motor temperature.
When the parameter is set to 100%, the maximum load
is taken as the value of parameter 99.6 Motor nominal
current (higher loads heat up the motor). The load curve
level should be adjusted if the ambient temperature
differs from the nominal value set in 35.50 Motor
ambient temperature.
I
= Motor current
I
N
= Nominal motor current
Drive output
frequency
I/I
N
(%)
150
100
50
35.52
35.53
35.51
Motor load curve35.51