Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
1 = Yes: An FPTC-xx module has been detected in slot
3.
Module found in slot
3
b6
1 = Yes: The module in slot 3 has an active fault (4993
Safe motor temperature 3).
Fault active in slot 3b7
1 = Yes: The module in slot 3 has an active warning
(A499 Motor temperature 3).
Warning active in
slot 3
b8
Reservedb9…15
1 = 10000h…FFFFh
- / real32Displays the motor overload level as a percent of the
motor overload fault limit. See parameter 35.56 Motor
overload action and section Motor overload
protection (page 115).
Motor overload level35.5
10 = 1 % / 10 = 1 %Motor overload level.
0.0% No motor overloading.
88.0% Motor overloaded to warning level.
100.0% Motor overloaded to fault level.
0.0 ... 300.0 %
- / uint16Shows temperature calibration status word.Temperature
Calibration status
word
35.9
Calibration status of temperature 1. See parameter
35.17 Temperature 1 calibration.
Temperature 1
calibration done
b0
Calibration status of temperature 2. See parameter
35.27 Temperature 2 calibration.
Temperature 2
calibration done
b1
Reservedb2…15
1 = 10000h…FFFFh
Disabled / uint16Selects the source from which measured temperature
1 is read.
For wiring examples, see the hardware manual of the
drive.
Usually this source is from a sensor connected to the
motor controlled by the drive, but it could be used to
measure and monitor a temperature from other parts
of the process as long as a suitable sensor is used as
per the selection list.
Temperature 1
source
35.11
0None. Temperature monitoring function 1 is disabled.Disabled
1Estimated motor temperature (see parameter 35.1
Motor estimated temperature).
The temperature is estimated from an internal drive
calculation. It is important to set up the ambient
temperature of the motor in 35.50 Motor ambient
temperature.
Estimated
temperature
Parameters 341