Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
1 = Force mode: Force AO1 to value of parameter 14.78
AO1 force data.
AO1b0
Reservedb1…15
1 = 10000h…FFFFh
- / real32(Visible when 14.1 Module 1 type = FAIO-01)
Displays the value of AO1 in mA.
This parameter is read-only.
AO1 actual value14.76
1000 = 1 mA / 1000 =
1 mA
Value of AO1.0.000 ... 22.000 mA
Zero / uint32(Visible when 14.1 Module 1 type = FAIO-01)
Selects a signal to be connected to analog output AO1.
Alternatively, sets the output to excitation mode to
feed a constant current to a temperature sensor.
AO1 source14.77
0NoneZero
11.1 Motor speed used (page 134).Motor speed used
31.6 Output frequency (page 134).Output frequency
41.7 Motor current (page 134).Motor current
61.10 Motor torque (page 134).Motor torque
71.11 DC voltage (page 135).DC voltage
81.14 Output power (page 135).Power inu out
1023.1 Speed ref ramp input (page 270).Speed ref ramp in
1123.2 Speed ref ramp output (page 270).Speed ref ramp out
1224.1 Used speed reference (page 277).Speed ref used
1326.2 Torque reference used (page 297).Torq ref used
See Terms and abbreviations (page 130).Other [value]
20The output is used to feed an excitation current to 1…3
Pt100 sensors. See section Motor thermal
protection (page 111).
Force Pt100
excitation
21The output is used to feed an excitation current to a
KTY84 sensor. See section Motor thermal
protection (page 111).
Force KTY84
excitation
22The output is used to feed an excitation current to 1…3
PTC sensors. See section Motor thermal
protection (page 111).
Force PTC excitation
23The output is used to feed an excitation current to 1…3
Pt1000 sensors. See section Motor thermal
protection (page 111).
Force Pt1000
excitation
3713.91 AO1 data storage.AO1 data storage
3813.92 AO2 data storage.AO2 data storage
- / real32(Visible when 14.1 Module 1 type = FIO-11)
Forced value that can be used instead of the selected
output signal. See parameter 14.71 AO force selection.
AO1 force data14.78
220 Parameters