Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Enable / uint16Enables/disables speed controller adaptation based
on motor flux reference (1.24 Flux actual %).
The proportional gain of the speed controller is
multiplied by a coefficient of 0…1 between 0…100%
flux reference respectively.
See also the block diagram on page 652.
Coefficient for K
p
(proportional gain)
1.000
0.000
0
100
Flux reference
(
01.24
) (%)
Flux adaptation
enable
25.30
0Speed controller adaptation based on flux reference
disabled
Disable
1Speed controller adaptation based on flux reference
enabled.
Enable
Parameters 293