Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Zero / uint32Selects the signal to be monitored by signal supervision
function 1.
Supervision 1 signal32.7
0None.Zero
11.1 Motor speed used.Speed
31.6 Output frequency.Frequency
41.7 Motor current.Current
61.10 Motor torque.Torque
71.11 DC voltage.DC voltage
81.14 Output power.Output power
912.11 AI1 actual value.AI1
1012.21 AI2 actual value (page 189).AI2
1823.1 Speed ref ramp input (page 270).Speed ref ramp in
1923.2 Speed ref ramp output (page 270).Speed ref ramp out
2024.1 Used speed reference (page 277).Speed ref used
2126.2 Torque reference used (page 297).Torque ref used
See Terms and abbreviations (page 130).Other [value]
0.000 s / real32Defines a filter time constant for the signal monitored
by signal supervision 1.
Supervision 1 filter
time
32.8
1000 = 1 s / 1000 = 1
s
Signal filter time.0.000 ... 30.000 s
0.00 / real32Defines the lower limit for signal supervision 1.Supervision 1 low32.9
- / -Low limit.-21474830.00 ...
21474830.00
0.00 / real32Defines the upper limit for signal supervision 1.Supervision 1 high32.10
- / -Upper limit.-21474830.00 ...
21474830.00
Disabled / uint16Selects the mode of signal supervision function 2.
Determines how the monitored signal (see parameter
32.17) is compared to its lower and upper limits (32.19
and 32.20 respectively).
The action to be taken when the condition is fulfilled
is selected by 32.16.
Supervision 2
function
32.15
0Signal supervision 2 not in use.Disabled
1Action is taken whenever the signal falls below its lower
limit.
Low
2Action is taken whenever the signal rises above its
upper limit.
High
3Action is taken whenever the absolute value of the
signal falls below its (absolute) lower limit.
Abs low
4Action is taken whenever the absolute value of the
signal rises above its (absolute) upper limit.
Abs high
Parameters 329