Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
3Motor overload class 30.Class 30
4Motor overload class 40.Class 40
0.0 % / real32Shows the calculated temperature of the motor cable.
See section Thermal protection of motor
cable (page 116).
102% = overtemperature warning (A480 Motor cable
overload)
106% = overtemperature fault (4000 Motor cable
overload)
This parameter is read-only.
Cable temperature35.60
1 = 1 % / 10 = 1 %Calculated temperature of motor cable.0.0 ... 200.0 %
10000.00 A / real32Specifies the continuous current of the motor cable
for the thermal protection function in the control
program.
WARNING!
The value entered in this parameter must be
limited according to all factors affecting the
loadability of the cable, such as ambient
temperature, cabling arrangement, and
shrouding. Refer to the technical data from the
cable manufacturer.
Cable nominal
current
35.61
1 = 1 A / 100 = 1 AContinuous current-carrying capacity of motor cable.0.00 ... 10000.00 A