Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
3This setting is to be used by ABB-authorized service
personnel only.
Custom
Disabled / uint16Enables signal injection. A high-frequency alternating
signal is injected into the motor at low speeds to
improve the stability of torque control. Signal injection
can be enabled with different amplitude levels.
Note: This is an expert level parameter and should not
be adjusted without appropriate skill.
Note: Use as low a level as possible that gives
satisfactory performance.
Note: Signal injection cannot be applied to
asynchronous motors.
Signal injection97.10
0Signal injection disabled.Disabled
1Signal injection enabled with an amplitude level of 5%.Enabled (5 %)
2Signal injection enabled with an amplitude level of 10%.Enabled (10 %)
3Signal injection enabled with an amplitude level of 15%.Enabled (15 %)
4Signal injection enabled with an amplitude level of 20%.Enabled (20 %)
100 % / real32Rotor time constant tuning.
This parameter can be used to improve torque accuracy
in closed-loop control of an induction motor. Normally,
the motor identification run provides sufficient torque
accuracy, but manual fine-tuning can be applied in
exceptionally demanding applications to achieve
optimal performance.
Note: This is an expert level parameter and should not
be adjusted without appropriate skill.
TR tuning97.11
1 = 1 % / 100 = 1 %Rotor time constant tuning.25...400 %
Parameters 529