What to doCause
Event name /
Aux. code
Code
(hex)
Check encoder settings (92 Encoder
1 configuration or 93 Encoder 2
configuration).
Encoder not configured.0004
Use parameter 91.10 Encoder
parameter refresh) to validate any
changes in the settings.
Check encoder status.Encoder stopped working.0005
Check the settings of parameters 31.32
Emergency ramp supervision and 31.33
Emergency ramp supervision delay.
Emergency stop did not finish within
expected time.
Emergency
ramp failed
73B0
Check the predefined ramp times
(23.1123.19 for mode Off1, 23.23 for
mode Off3).
Check the settings of parameters 31.37
Ramp stop supervision and 31.38
Ramp stop supervision delay.
Ramp stop did not finish within
expected time.
Stop failed73B1
Check the predefined ramp times in
parameter group 23 Speed reference
ramp.
Without a dual-use license, the fault
limit is 598 Hz. Contact your local ABB
Maximum allowed output frequency
exceeded.
Overfrequency73F0
representative for dual-use licensing
information.
Check status of fieldbus
communication.
Cyclical communication between drive
and fieldbus adapter module A or
FBA A
communication
7510
See user documentation of fieldbus
interface.
between PLC and fieldbus adapter
module A is lost.
Check settings of parameter groups
50 Fieldbus adapter (FBA), 51 FBA A
settings, 52 FBA A data in and 53 FBA
A data out.
Check cable connections.
Check if communication master is able
to communicate.
Check communication connections
between adapter and drive.
Communication problem between
adapter and drive.
0002
Check communication connections
between adapter and PLC. Stop
Communication problem between
adapter and PLC or parameters
0003
using parameter 51.27 FBA A par
refresh to refresh parameters.
refreshed using the parameter 51.27
FBA A par refresh.
Check fieldbus communication
adapter.
Lost communication with fieldbus
communication adapter.
0004
Contact your local ABB
representative.
Unknown internal issues.Other aux code value
Check status of fieldbus
communication.
Cyclical communication between drive
and fieldbus adapter module B or
FBA B
communication
7520
See user documentation of fieldbus
interface.
between PLC and fieldbus adapter
module B is lost.
Check settings of parameter group 50
Fieldbus adapter (FBA).
Check cable connections.
Fault tracing 567