Fault tracing
313
2080 ENC 2 PULSE
FREQUENCY
(0x738C)
Encoder 2 is receiving too high
data flow (pulse frequency).
Check encoder settings.
Change parameters 93.03 ENC1 SP
CALCMODE and 93.13 ENC2 SP
CALCMODE to use only one channel pulses/
edges.
2082 BR DATA
(0x7113)
Brake chopper is configured
wrong.
Check the brake chopper configuration in
parameter group 48.
Code Alarm
(fieldbus code)
Cause What to do