Standard function blocks
401
Switch & Demux
DEMUX-I
(10061)
Illustration
Execution time 1.38 µs (when two outputs are used) + 0.30 µs (for every additional output). When all
outputs are used, the execution time is 10.38 µs.
Operation Input (I) value is stored to the output (OA1…OA32) selected by the address input (A).
All other outputs are 0.
If the address input is 0, negative or exceeds the number of the outputs, all outputs are
0.
Inputs The input data type is selected by the user.
Address input (A): DINT
Input (I): INT, DINT, Boolean, REAL, REAL24
Outputs The number of the output channels (1…32) is selected by the user.
Output (OA1…OA32): INT, DINT, REAL, REAL24, Boolean
DEMUX-MI
(10062)
Illustration
Execution time 0.99 µs (when two outputs are used) + 0.25 µs (for every additional output). When all
outputs are used, the execution time is 8.4 µs.
DEMUX-I
(BOOL) 81
TLA1 1 msec (1)
A
I
OA1
OA1(81)
OA2
OA2(81)
DEMUX-MI
(BOOL) 82
TLA1 1 msec (1)
A
R
L
S
I
OA1
OA1(82)
OA2
OA2(82)