Loading...
Standard function blocks
372
FIO_01_slot2
(10085)
Illustration
Execution time 8.6 µs
Operation The block controls the four digital inputs/outputs (DIO1…DIO4) and two relay outputs
(RO1, RO2) of a FIO-01 Digital I/O Extension mounted on slot 2 of the drive control unit.
The state of a DIOx conf input of the block determines whether the corresponding DIO
on the FIO-01 is an input or an output (0 = input, 1 = output). If the DIO is an output, the
DOx input of the block defines its state.
The RO1 and RO2 inputs define the state of the relay outputs of the FIO-01 (0 = not
energised, 1 = energised).
The DIx outputs show the state of the DIOs.
Inputs Digital input/output mode selection (DIO1 conf DIO4 conf): Boolean
Digital output state selection (DO1…DO4): Boolean
Relay output state selection (RO1, RO2): Boolean
Outputs Digital input/output state (DI1…DI4): Boolean
Error output (Error): DINT (0 = No error; 1 = Application program memory full)
FIO_01_slot2
50
TLA1 1 msec (1)
DIO1 conf
DIO2 conf
DIO3 conf
DIO4 conf
DO1
DO2
DO3
DO4
RO1
RO2
DI1
DI1(50)
DI2
DI2(50)
DI3
DI3(50)
DI4
DI4(50)
Error
Error(50)