Parameters and firmware blocks
178
Group 33 SUPERVISION
Configuration of signal supervision.
33
Firmware block:
SUPERVISION
(17)
Block outputs located in other
parameter groups
6.14 SUPERV STATUS (page 112)
33.01 SUPERV1 FUNC FW block: SUPERVISION (see above)
Selects the mode of supervision 1.
(0) Disabled Supervision 1 not in use.
(1) Low When the signal selected by parameter 33.02 SUPERV1 ACT falls
below the value of parameter 33.04 SUPERV1 LIM LO, bit 0 of 6.14
SUPERV STATUS is activated. To clear the bit, the signal must
exceed the value of parameter 33.03 SUPERV1 LIM HI.
(2) High When the signal selected by parameter 33.02 SUPERV1 ACT
exceeds the value of parameter 33.03 SUPERV1 LIM HI, bit 0 of 6.14
SUPERV STATUS is activated. To clear the bit, the signal must fall
below the value of parameter 33.04 SUPERV1 LIM LO.
(3) Abs Low When the absolute value of the signal selected by parameter 33.02
SUPERV1 ACT falls below the value of parameter 33.04 SUPERV1
LIM LO, bit 0 of 6.14 SUPERV STATUS is activated. To clear the bit,
the absolute value of the signal must exceed the value of parameter
33.03 SUPERV1 LIM HI.
(4) Abs High When the absolute value of the signal selected by parameter 33.02
SUPERV1 ACT exceeds the value of parameter 33.03 SUPERV1 LIM
HI, bit 0 of 6.14 SUPERV STATUS is activated. To clear the bit, the
absolute value of the signal must fall below the value of parameter
33.04 SUPERV1 LIM LO.
33.02 SUPERV1 ACT FW block: SUPERVISION (see above)
Selects the signal to be monitored by supervision 1. See parameter 33.01 SUPERV1 FUNC.
Value pointer: Group and index
SUPERVISION
45
TLF 11 10 msec (6)
33.01 SUPERV1 FUNC
[ Disabled ]
< 33.02 SUPERV1 ACT
[ SPEED ACT ]
(7 / 1.01)
33.03 SUPERV1 LIM HI
[ 0.00 ]
33.04 SUPERV1 LIM LO
[ 0.00 ]
33.05 SUPERV2 FUNC
[ Disabled ]
< 33.06 SUPERV2 ACT
[ CURRENT ]
(1 / 1.04)
33.07 SUPERV2 LIM HI
[ 0.00 ]
33.08 SUPERV2 LIM LO
[ 0.00 ]
33.09 SUPERV3 FUNC
[ Disabled ]
< 33.10 SUPERV3 ACT
[ TORQUE ]
(1 / 1.06)
33.11 SUPERV3 LIM HI
[ 0.00 ]
33.12 SUPERV3 LIM LO
[ 0.00 ]
6.14 SUPERV STATUS