Parameter data
284
Actual signals (Parameter groups 1…9)
Index Name Type Range Unit FbEq Update
time
Data
length
PT Save
PF
Page
no.
01 ACTUAL VALUES
1.01 SPEED ACT REAL -30000…30000 rpm 1 = 100 250 µs 32 WP 91
1.02 SPEED ACT PERC REAL -1000…1000 % 1 = 100 2 ms 32 WP 91
1.03 FREQUENCY REAL -30000…30000 Hz 1 = 100 2 ms 32 WP 91
1.04 CURRENT REAL 0…30000 A 1 = 100 10 ms 32 WP 91
1.05 CURRENT PERC REAL 0…1000 % 1 = 10 2 ms 16 WP 91
1.06 TORQUE REAL -1600…1600 % 1 = 10 2 ms 16 WP 91
1.07 DC-VOLTAGE REAL - V 1 = 100 2 ms 32 WP 91
1.08 ENCODER 1 SPEED REAL - rpm 1 = 100 250 µs 32 WP 91
1.09 ENCODER 1 POS REAL24 - rev 1=100000000 250 µs 32 WP 91
1.10 ENCODER 2 SPEED REAL - rpm 1 = 100 250 µs 32 WP 92
1.11 ENCODER 2 POS REAL24 - rev 1=100000000 250 µs 32 WP 92
1.12 POS ACT REAL -32768…32767 * See 60.09 250 µs 32 WP 92
1.13 POS 2ND ENC REAL -32768…32767 revs 1 = 1 250 µs 32 WP 92
1.14 SPEED ESTIMATED REAL -30000…30000 rpm 1 = 100 2 ms 32 WP 92
1.15 TEMP INVERTER REAL24 -40…160 °C 1 = 10 2 ms 16 WP 92
1.16 TEMP BC REAL24 -40…160 °C 1 = 10 2 ms 16 WP 92
1.17 MOTOR TEMP REAL -10…250 °C 1 = 10 10 ms 16 WP 92
1.18 MOTOR TEMP EST INT32 -60…1000 °C 1 = 1 10 ms 16 WP x 92
1.19 USED SUPPLY VOLT REAL 0…1000 V 1 = 10 10 ms 16 WP 92
1.20 BRAKE RES LOAD REAL24 0…1000 % 1 = 1 50 ms 16 WP 92
1.21 CPU USAGE UINT32 0…100 % 1 = 1 100 ms 16 WP 92
1.22 INVERTER POWER REAL -2
31
…2
31
- 1 kW 1 = 100 10 ms 32 WP 92
1.26 ON TIME COUNTER INT32 0…35791394.1 h 1 = 100 10 ms 32 WP0 x 92
1.27 RUN TIME COUNTER INT32 0…35791394.1 h 1 = 100 10 ms 32 WP0 x 93
1.28 FAN ON-TIME INT32 0…35791394.1 h 1 = 100 10 ms 32 WP0 x 93
1.31 MECH TIME CONST REAL 0…32767 s 1 = 1000 10 ms 32 WP x 93
1.38 TEMP INT BOARD REAL24 -40…160 °C 1 = 10 2 ms 16 WP 93
1.39 OUTPUT VOLTAGE REAL 0…1000 V 1 = 1 10 ms 16 WP 93
1.42 FAN START COUNT INT32 0...2147483647 - 1 = 1 10 ms 32 WP x 93
02 I/O VALUES
2.01 DI STATUS Pb 0…0x3F - 1 = 1 2 ms 16 WP 94
2.02 RO STATUS Pb - - 1 = 1 2 ms 16 WP 94
2.03 DIO STATUS Pb - - 1 = 1 2 ms 16 WP 94
2.04 AI1 REAL - V or mA 1 = 1000 2 ms 16 WP 94
2.05 AI1 SCALED REAL - - 1 = 1000 250 µs 32 WP 94
2.06 AI2 REAL - V or mA 1 = 1000 2 ms 16 WP 94
2.07 AI2 SCALED REAL - - 1 = 1000 250 µs 32 WP 94
2.08 AO1 REAL - mA 1 = 1000 2 ms 16 WP 94
2.09 AO2 REAL - V 1 = 1000 2 ms 16 WP 94
2.10 DIO2 FREQ IN REAL -32768…32768 - 1 = 1000 2 ms 32 WP 94
2.11 DIO3 FREQ OUT REAL -32768…32768 Hz 1 = 1000 2 ms 32 WP 94