Standard function blocks
361
Counters
CTD
(10047)
Illustration
Execution time 0.92 µs
Operation The counter output (CV) value is decreased by 1 if the counter input (CD) value
changes from 0 -> 1 and the load input (LD) value is 0. If the load input value is 1, the
preset input (PV) value is stored as the counter output (CV) value. If the counter output
has reached its minimum value -32768, the counter output remains unchanged.
The status output (Q) is 1 if the counter output (CV) value <
0.
Example:
Inputs Load input (LD): Boolean
Counter input (CD): Boolean
Preset input (PV): INT
Outputs Counter output (CV): INT
Status output (Q): Boolean
CTD
93
TLA1 1 msec (1)
LD
>CD
PV
CV
CV(93)
Q
Q(93)
LD CD PV Q CV
prev
CV
01 -> 010 05 5
0 0 -> 1 10 0 5 5 - 1 = 4
11 -> 0-2 14 -2
10 -> 11 0-2 1
0 0 -> 1 5 1 1 1 -1 = 0
1 1 -> 0 -32768 1 0 -32768
0 0 -> 1 10 1 -32768 -32768
CV
prev
is the previous cycle counter output value.

Table of Contents

Other manuals for ABB ACSM1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACSM1 and is the answer not in the manual?

ABB ACSM1 Specifications

General IconGeneral
Protection ClassIP20
Voltage Range380 V to 480 V
Product Type DesignationACSM1
Input Voltage380-480 V AC
Communication InterfacesModbus RTU
Protection FeaturesOvercurrent, overvoltage, undervoltage, short circuit, overload, overtemperature
Operating Temperature-10°C to +40°C
Storage Temperature-40°C to +70°C
Humidity5% to 95% (non-condensing)
AltitudeUp to 1000 m

Related product manuals