Standard function blocks
375
FIO_11_AI_slot2
(10089)
Illustration
Execution time 11.1 µs
Operation The block controls the three analogue inputs (AI1…AI3) of a FIO-11 Analog I/O
Extension mounted on slot 2 of the drive control unit.
The block outputs both the unscaled (AIx) and scaled (AIx scaled) actual values of each
analogue input. The scaling is based on the relationship between the ranges
AIx min AIx max and AIx min scale AIx max scale.
AIx Min must be smaller than AIx Max; AIx Max Scale can be greater or smaller than AIx
Min Scale.
FIO_11_AI_slot2
52
TLA1 1 msec (1)
AI1 fi lt gain
AI1 Min
AI1 Max
AI1 Min scal e
AI1 Max scale
AI2 fi lt gain
AI2 Min
AI2 Max
AI2 Min scal e
AI2 Max scale
AI3 fi lt gain
AI3 Min
AI3 Max
AI3 Min scal e
AI3 Max scale
AI1 mode
AI1 mode(5 2)
AI1
AI1(52)
AI1 scaled
AI1 scaled(52)
AI2 mode
AI2 mode(5 2)
AI2
AI2(52)
AI2 scaled
AI2 scaled(52)
AI3 mode
AI3 mode(5 2)
AI3
AI3(52)
AI3 scaled
AI3 scaled(52)
Error
Error(52)
AIx scaled
32768
AIx [V or mA]
11 V or
-11 V or
AIx Max
AIx Min
AIx Max Scale
AIx Min Scale
-22 mA
22 mA
AIx Min Scale < AIx Max Scale
-32768