Parameters and firmware blocks
211
Group 52 FBA DATA IN
These parameters select the data to be sent by the drive to the fieldbus controller,
and need to be set only if a fieldbus adapter module is installed. See also Appendix
A – Fieldbus control on page 423.
Notes:
This parameter group is presented in the User’s Manual of the fieldbus adapter as
parameter group 3 or C.
The new settings will take effect when the drive is powered up the next time
(before powering off the drive, wait at least 1 minute), or when parameter 51.27
FBA PAR REFRESH is activated.
The maximum number of data words is protocol-dependent.
52
52.01 FBA DATA IN1 FW block: None
Selects data to be transferred from the drive to the fieldbus controller.
0 Not in use.
4 Status Word (16 bits).
5 Actual value 1 (16 bits).
6 Actual value 2 (16 bits).
14 Status Word (32 bits).
15 Actual value 1 (32 bits).
16 Actual value 2 (32 bits).
101…9999 Parameter index.
52.02 FBA DATA IN2 FW block: None
……
52.12 FBA DATA IN12 FW block: None
See 52.01 FBA DATA IN1.