Parameters and firmware blocks
275
Group 99 START-UP DATA
Start-up settings such as language, motor data and motor control mode.
The nominal motor values must be set before the drive is started; for detailed
instructions, see chapter Start-up on page 15.
With DTC motor control mode, parameters 99.0699.10 must be set; better control
accuracy is achieved by also setting parameters 99.11 and 99.12.
With scalar control, parameters 99.0699.09 must be set.
99
99.01 LANGUAGE FW block: None
Selects the language.
Note: Not all languages listed below are necessarily supported.
(0809h) ENGLISH English.
(0407h) DEUTSCH German.
(0410h) ITALIANO Italian.
(040Ah) ESPAÑOL Spanish.
(041Dh) SVENSKA Swedish.
(041Fh) TÜRKÇE Turkish.
99.04 MOTOR TYPE FW block: None
Selects the motor type.
Note: This parameter cannot be changed while the drive is running.
(0) AM Asynchronous motor. Three phase AC voltage supplied induction
motor with squirrel cage rotor.
(1) PMSM Permanent magnet motor. Three phase AC voltage supplied
synchronous motor with permanent magnet rotor and sinusoidal
BackEMF voltage.