Parameters and firmware blocks
277
99.08 MOT NOM FREQ FW block: None
Defines the nominal motor frequency.
Note: This parameter cannot be changed while the drive is running.
5…500 Hz Nominal motor frequency.
99.09 MOT NOM SPEED FW block: None
Defines the nominal motor speed. Must be equal to the value on the motor rating plate. When
parameter value is changed, check the speed limits in parameter group 20.
Note: This parameter cannot be changed while the drive is running.
Note: For safety reasons, after motor ID run, the maximum and minimum speed limits (parameters
20.01 and 20.02) are automatically set to a 1.2 times bigger value than the nominal motor speed.
0…30000 rpm Nominal motor speed.
99.10 MOT NOM POWER FW block: None
Defines the nominal motor power. Must be equal to the value on the motor rating plate. If several
motors are connected to the inverter, enter the total power of the motors. Set also parameter 99.11
MOT NOM COSFII.
Note: This parameter cannot be changed while the drive is running.
0…10000 kW Nominal motor power.
99.11 MOT NOM COSFII FW block: None
Defines the cosphi (not applicable to permanent magnet motors) for a more accurate motor model.
Not obligatory; if set, should be equal to the value on the motor rating plate.
Note: This parameter cannot be changed while the drive is running.
0…1 Cosphi (0 = parameter disabled).
99.12 MOT NOM TORQUE FW block: None
Defines the nominal motor shaft torque for a more accurate motor model. Not obligatory.
Note: This parameter cannot be changed while the drive is running.
0…2147483 Nm Nominal motor shaft torque.