Standard function blocks
344
Communication
See also Appendix B – Drive-to-drive link (page 431).
D2D_Conf
(10092)
Illustration
Execution time -
Operation Defines handling interval for drive-to-drive references 1 and 2, and the address (group
number) for standard (non-chained) multicast messages.
The values of the Ref1/2 Cycle Sel inputs correspond to the following intervals:
Note: Negative value of Ref2 Cycle Sel disables the handling of Ref2 (if disabled in the
master, it must be disabled in all follower drives as well).
Allowable values for the Std Mcast Group input are 0 (= multicasting not used) and
1…62 (multicast group).
An unconnected input, or an input in an error state, is interpreted as having the value 0.
The error codes indicated by the Error output are as follows:
See also section Examples of using standard function blocks in drive-to-drive
communication starting on page 439.
Inputs Drive-to-drive reference 1 handling interval (Ref1 Cycle Sel): INT
Drive-to-drive reference 2 handling interval (Ref2 Cycle Sel): INT
Standard multicast address (Std Mcast Group): INT
Outputs Error output (Error): PB
D2D_Conf
70
TLA1 1 msec (1)
Ref1 Cycle Se l
Ref2 Cycle Se l
Std Mcast Group
Error
Error(70)
Value Handling interval
0 Default (500 µs for reference 1; 2 ms for reference 2)
1 250 µs
2 500 µs
32 ms
Bit Description
0 REF1_CYCLE_ERR: Value of input Ref1 Cycle Sel out of range
1 REF2_CYCLE_ERR: Value of input Ref2 Cycle Sel out of range
2 STD_MCAST_ERR: Value of input Std Mcast Group out of range