Parameters and firmware blocks
214
Group 57 D2D COMMUNICATION
Drive-to-drive communication settings. See Appendix B – Drive-to-drive link on page
431.
57
Firmware block:
D2D COMMUNICATION
(57)
This block sets up the drive-to-drive
communication. It also shows the
main drive-to-drive control word and
the two references.
Block outputs located in other
parameter groups
2.17 D2D MAIN CW (page 100)
2.19 D2D REF1 (page 100)
2.20 D2D REF2 (page 100)
57.01 LINK MODE FW block: D2D COMMUNICATION (see above)
Activates the drive-to-drive connection.
(0) Disabled Drive-to-drive connection disabled.
(1) Follower The drive is a follower on the drive-to-drive link.
(2) Master The drive is the master on the drive-to-drive link. Only one drive can
be the master at a time.
57.02 COMM LOSS FUNC FW block: D2D COMMUNICATION (see above)
Selects how the drive acts when an erroneous drive-to-drive configuration or a communication break
is detected.
(0) No Protection inactive.
(1) Alarm The drive generates an alarm.
(2) Fault The drive trips on a fault.
D2D COMMUNICATION
44
TLF9 500 µsec (2)
57.01 LINK MODE
[ Disabled ]
57.02 COMM LOSS FUNC
[ Alarm ]
57.03 NODE ADDRESS
[ 1 ]
57.04 FOLLOWER MASK 1
[ 0000 0000 ]
57.05 FOLLOWER MASK 2
[ 0000 0000 ]
< 57.06 REF 1 SRC
[ SPEED REF RAMPED ]
(6 / 3.04)
< 57.07 REF 2 SRC
[ TO RQ REF TO TC ]
(8 / 3.13)
< 57.08 FOLLOWER CW SRC
[ D2D FOLLOWER CW ]
(4 / 2.18)
57.09 KERNEL SYNC MODE
[ NoSync ]
57.10 KERNEL SYNC OFFS
[ 0.000 ms ]
57.11 REF 1 MSG TYPE
[ Broadcast ]
57.12 REF1 MC GROUP
[ 0 ]
57.13 NEXT REF1 MC GRP
[ 0 ]
57.14 NR REF1 MC GRPS
[ 1 ]
2.17 D2D MAIN CW
2.19 D2D REF1
2.20 D2D REF2