Parameters and firmware blocks
176
Firmware block:
TORQ REF MOD
(33)
This block
selects the source for the torque
reference
scales the input torque reference
according to the defined load share
factor
defines limits for the torque
reference
defines ramp-up and ramp-down
times for the torque reference
shows the ramped torque reference
value and the torque reference
value limited by the rush control.
Block outputs located in other
parameter groups
3.10 TORQ REF RAMPED (page 101)
3.11 TORQ REF RUSHLIM (page 101)
32.03 TORQ REF IN FW block: TORQ REF MOD (see above)
Selects the source for the torque reference input for the torque ramp function. The default value is
P.3.9, ie, signal 3.09 TORQ REF1, which is the output of the TORQ REF SEL firmware block.
Value pointer: Group and index
32.04 MAXIMUM TORQ REF FW block: TORQ REF MOD (see above)
Defines the maximum torque reference.
0…1000% Maximum torque reference.
32.05 MINIMUM TORQ REF FW block: TORQ REF MOD (see above)
Defines the minimum torque reference.
-1000…0% Minimum torque reference.
32.06 LOAD SHARE FW block: TORQ REF MOD (see above)
Scales the external torque reference to a required level (external torque reference is multiplied by the
selected value).
Note: If local torque reference is used, no load share scaling is applied.
-8…8 External torque reference multiplier.
32.07 TORQ RAMP UP FW block: TORQ REF MOD (see above)
Defines the torque reference ramp-up time, ie, the time for the reference to increase from zero to the
nominal motor torque.
0…60 s Torque reference ramp-up time.
TORQ REF MOD
2
TRQREF 500 µsec (2)
< 32.03 TORQ REF IN
[ TORQ REF1 ]
(8 / 3.09)
32.04 MAXIMUM TORQ REF
(Drive value)
32.05 MINIMUM TORQ REF
(Drive value)
32.06 LOAD SHARE
(Drive value)
32.07 TORQ RAMP UP
(Drive value)
32.08 TORQ RAMP DOWN
(Drive value)
32.09 RUSH CTRL GAIN
(Drive value)
32.10 RUSH CTRL TI
(Drive value)
3.10 TORQ REF RAMPED
3.11 TORQ REF RUSHLIM

Table of Contents