Standard function blocks
376
The AIx filt gain inputs determine a filtering time for each input as follows:
The AIx mode outputs show whether the corresponding input is voltage (0) or current
(1). The voltage/current selection is made using the hardware switches on the FIO-11.
Inputs Analogue input filter gain selection (AI1 filt gain AI3 filt gain): INT
Minimum value of input signal (AI1 Min AI3 Min): REAL (>
-11 V or -22 mA)
Maximum value of input signal (AI1 Max AI3 Max): REAL (< 11 V or 22 mA)
Minimum value of scaled output signal (AI1 Min scale AI3 Min scale): REAL
Maximum value of scaled output signal (AI1 Max scale AI3 Max scale): REAL
Outputs Analogue input mode (voltage or current) (AI1 mode AI3 mode): Boolean
Value of analogue input (AI1 AI3): REAL
Scaled value of analogue input (AI1 scaled AI3 scaled): REAL
Error output (Error): DINT (0 = No error; 1 = Application program memory full)
AIx scaled
32768
AIx [V or mA]
11 V or
-11 V or
AIx Max
AIx Min
AIx Min Scale
AIx Max Scale
-22 mA
22 mA
AIx Min Scale > AIx Max Scale
-32768
AIx filt gain Filtering time Notes
0 No filtering
1 125 µs Recommended setting
2 250 µs
3 500 µs
41 ms
52 ms
64 ms
7 7.9375 ms