Standard function blocks
406
Operation The output (Q) is set to 1 when the input (IN) has been 1 for a time defined by the pulse
time input (PT). The output is set to 0, when the input is set to 0.
Elapsed time count (ET) starts when the input is set to 1 and stops when the input is set
to 0.
Example:
Inputs Input (IN): Boolean
Pulse time input (PT): DINT (1 = 1 µs)
Outputs Elapsed time output (ET): DINT (1 = 1 µs)
Output (Q): Boolean
TP
(10060)
Illustration
Execution time 1.46 µs
Operation The output (Q) is set to 1 when the input (IN) is set to 1. The output is set to 0, when it
has been 1 for a time defined by the pulse time input (PT).
Elapsed time count (ET) starts when the input is set to 1 and stops when the input is set
to 0.
Inputs Pulse time input (PT): DINT (1 = 1 µs)
Input (IN): Boolean
Outputs Output (Q): Boolean
Elapsed time output (ET): DINT (1 = 1 µs)
IN
Q
PT
PT
ET
ET
ET
TP
88
TLA1 1 msec (1)
PT
>IN
Q
Q(88)
ET
ET(88)
IN
Q
ET
PT
PT
PT